 |
|
As seen in

January,
2004
|
|
Digital SCR Power Controllers Reduce Energy
Costs
By
Chris McCormick, Spang Power Electronics, Mentor, Ohio and
Tim Horning, Signature Vacuum Systems Inc., Meadville, Pa.
|
|
Application of
digital SCR (silicon controlled rectifier) power control technology
saved a supplier to the glass coatings industry big dollars in real
utility power costs, which gave a payback on the investment on one
month.
 Three-zone SCR power center for
nickel-chromium heating
applications |
Digital SCR
(silicon controlled rectifier) power control
technology was successfully incorporated into two new furnaces in
an expansion of the thermal processing department for a supplier
to the glass coatings industry, resulting in saving over $2000 per
month in real utility power costs. Digital SCR power controllers
have the flexibility to control power in the synchronous
(zero-cross) mode firing into a transformer coupled resistive
heater load. Traditional design dictates phase-angle firing of the
power controller to avoid the pitfalls of transformer core
saturation.
|
|
Background
 Fig 1 Spang 853 digital SCR power
controller |
Signature
Vacuum Systems Inc. was contracted to build and
install two vacuum furnaces for the customer’s thermal-processing
department as part of a capacity expansion project. To maximize
energy savings for the customer, Signature Vacuum Systems opted to
use synchronous firing SCR power controllers to control the
furnace heat input. The controller selected was Spang Power
Electronics 853, three-phase, digital ac power controller (Fig.1).
A factor in selecting the Spang 853 digital SCR power
controller is the unit’s ability to fire the SCRs directly into
transformers in either phase-angle or synchronous firing mode.
This provided an installation that could be operated initially in
phase-angle mode (the traditional method of control), and later
reprogrammed to zero-cross mode (the desired method of control).
This flexibility facilitated the comparison of process quality and
power cost levels.
The customer was accustomed to their existing phase angle-fired
systems. Using the dual firing mode capability of the 853
controller, the furnace control system was designed to permit the
operator to switch between synchronous and phase-angle firing “on
the fly.” This is accomplished via a Modbus serial link between
the operator interface panel and the power controller. This
flexibility gives the furnace operator the ability to monitor the
balance of voltage and current in phase-angle mode (for
short-circuit detection), and then switch to synchronous firing
for maximum operating economy.
The specific zone ratings for the installed furnaces are listed
below:
- Input voltage: 480 VAC
- Output voltage: 45 VAC
- Output current: 2,566 AAC
- Power rating: 200 kW
 Single-zone SCR power center for
platinum heating applications |
The two furnaces each contain two ~200-kW zones for a total of
800 kW. During operation, the furnaces represent about 50% of the
total facility power consumption. The installation used identical
power systems for each zone. In addition, each zone included an
853 digital SCR power controller and an output transformer feeding
the resistive heating elements.
|
|
Digital SCR Power Control
The 853 digital SCR power controller is a state-of-the-art
three-phase ac power controller built around digital
microprocessor technology. The processor power and flexibility
allowed the furnace supplier to:
- Integrate the power control into the automated furnace
control system
- Use software to select operating modes
- Connect to the instrument communication network
- Optimize the power controller parameters for the
application
- Provide improved process reliability and
troubleshooting
In this application, the power controllers included:
- Three-phase 350 AAC units
- Integral local digital controls
- Modbus connectivity to an automation direct PLC
- Fuseless design (eliminate I2T fusing)
- Ability to accept 4-20 mA analog input for temperature
control
|
|
Performance Analysis
The benefits analysis was based on the direct comparison of
phase-angle to zero-cross process heater control. Key to
quantifying the benefits from the use of the digital power
controllers are accurate process measurements. A Square D
Powerlogic Series 3000 circuit monitor was installed on the input
feed to the facility to measure the power parameters. Initially,
all zones were controlled in the phase angle-fired mode and
measurements recorded for the total process. Each zone was
sequentially reconfigured to zero-cross mode and measurements of
the same parameters taken at each stage. A summary of the data is
provided in Table 1. The data illustrates that the kW requirements
remained constant while the KVA demand was substantially reduced.
A corresponding increase in power factor (PF) occurred at each
stage.
The cost impact of this change in control
mode depended on the power costs actually charged to the customer.
The power consumption rate schedule applied to the facility by the
utility company is shown in Table 2. The energy cost analysis In
Table 3 is based on one month of continuous operation at a base load
of 900 kW. This analysis assumes all four zones running in either
phase-angle or zero-cross mode.

Other process and power consumption benefits were measured as a
result of the transition from phase angle to zero cross control.
Total harmonic distortion (THD) was reduced on the system. Table 4
shows the THD for both voltage and current as each zone was
changed from phase-angle to zero-cross control mode.

When firing SCR power controllers in zero cross mode,
consideration must be given to minimizing the power peaks, or
power pulsing, that are characteristic of this power control
method. (Power pulsing is sometimes detected in the flickering of
overhead lighting.) To minimize power pulsing in a multiple-zone
installation, the 853 digital SCR power controller provides the
functionality of node synchronization. Multiple units may be
configured to fire at staggered intervals to avoid simultaneous
turn-on and, thereby, minimize the power peaks. For example, if
two furnace zones are operating at 50% each, then each zone will
be ON for one cycle and then OFF for one cycle. Node
synchronization causes the two zones to alternate the ON period as
illustrated in Fig. 2. The resultant power draw from the
distribution system is constant, and peak power fluctuation is
zero. Applying this technique to multiple SCR power controllers
operating in zero-cross mode minimizes power fluctuation.
 Fig 2 Illustration of functionality of
node synchronization to minimize power pulsing in a
multiple-zone installation. Multiple units may be configured
to fire at staggered intervals to avoid simultaneous
turn-on, minimizing the power
peaks.
|
|
Conclusion
To validate the tangible benefits from the use of digital power
control technology, the customer isolated the process, conducted
comparative process measurements and calculated the cost benefits
from the use of the digital SCR power controllers. This resulted
in over $2000 per month savings in power costs. The pay back on
the additional investment was achieved through savings in the
first electric bill.
Measurable benefits of installing four 853, three-phase,
digital ac power controllers include:
- 5% reduction in monthly utility power costs
- 17.5% improvement in power factor
- 66% reduction in total voltage harmonic distortion
- 53% reduction in total current harmonic distortion
- Reduction in radio frequency interference (RFI)
- Virtual elimination of peak power
fluctuations
 Twenty-five zone SCR power center
(inside) for silicon-carbide heating
applications
Christopher
M. McCormick is the Industry Manager of AC Power Industries for
Spang Power Electronics, Mentor, OH. For more information about
Spang's power controllers, call (440) 352-8600 or visit www.spangpower.com.
|
to
What's New
|
|